Hydrolevel 3250 User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
11
YES
Recheck
Wiring.
Replace
Control.
When there is no call to fire the burner, the voltage
should be 0 volts between B1 and B2.
Make sure the burner is wired to B1.
YES
NO
Is the
Low Limit Dial
Set to OFF?
Is there
120 VAC between
B1 and B2?
NO
Is the
T
hermostat
(T-T) Calling
f
or Heat?
YES
Y
ES
Is the
External Zone
(ZC-ZR) Calling
for Heat?
N
O
NO
I
s the
Red LED
(LOW WATER)
On?
The Control is
S
ensing
Low Water.
WARNING!
T
URN OFF POWER TO BURNER IMMEDIATELY!
C
AUTION – ALWAYS ALLOW A BOILER TO FULLY COOL
BEFORE ADDING WATER.
Recheck wiring. Make sure that burner is wired to
B1. Burner should never fire when red or yellow
LED is lit.
Is either
Y
ellow LED
On?
T
he Control has
Reached Target
o
r High Limit
Temperature.
The Control is
Operating
Normally.
The Control is
Operating
Normally.
The burner will continue to fire when there is a call
f
rom the thermostat or external zone.
Check temperature display. When the Low Limit is
set, the HydroStat will fire the burner until the
temperature reaches the Low Limit Setting.
If there is no call for heat (from T-T, ZC-ZR or Low
Limit), there should be 0 VAC between B1-B2.
If there is voltage between B1-B2, the control
should be replaced.
Troubleshooting Flow Chart 2 Burner Will Not Shut Down
Y
ES
YES
NO
NO