10NOYES NOIs theThermostat (T-T) Calling for Heat?Is There120 VACBetween B1and B2?NOIs the External Zone(ZC-ZR) Callingfor Heat?NOIs theLow Limit Dial
11YESRecheckWiring.ReplaceControl.When there is no call to fire the burner, the voltageshould be 0 volts between B1 and B2. Make sure the burner is w
1283 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.comREMOTE MOUNTING KITSMAINTENANCERemove the Elec
2MOUNTING THE CONTROLSTEP 1Two mounting positionsare available on the back of the control(Fig. 1). Select which of the two positions(2 knockouts) is b
WIRING3STEP 1 Connect 120 VAC Hot to terminal L1. Connect120 VAC Neutral to terminal L2. Disconnect means andoverload protection as required (provide
4Connect thermostat or end switch from zone relay or multi-zonepanel to T-T. Connect circulator to C2-C1. Connect end switchfrom indirect zone relay t
5NOTE: The wire from ZR to the hot terminal of the indirect circulator will ensurethat indirect calls will fire to limit and receive priority over hea
SINGLE CIRCULATOR — Typical Multiple Zone Valve Panel with Indirect6ZONE/INDIRECTSWITCHPOSITIONZONE/INDIRECTSWITCHPOSITIONMULTIPLE CIRCULATORS — Typic
NOTE: Settings can be checked using the TEST/SETTINGS Button. See page 8 for details.Setting the High Limit The high limit is factory set at 190°F. To
8 TEMP ACTIVE Indicates that the Fuel SmartHydroStat control is powered and that the temperaturefunction is active. TEMP HI TEMP Illuminates when th
9TROUBLESHOOTINGBurner Will Not Fire See Flow Chart 1, page 10Burner Will Not Shut Down See Flow Chart 2, page 11Temperature Display ExceedsHigh Limit