TEMP ACTIVE Indicates that the HydroStat control is
powered and that the temperature function is active.
TEMP HIGH TEMP Illuminates when the boiler water
temperature reaches the high limit setting. It will remain lit
until the water temperature falls below the high limit setting
less the differential setting. The HydroStat control will prevent
burner operation while this LED is on. NOTE: This LED
illuminates regularly during normal boiler operation.
LWCO ACTIVE Indicates that the low water cut-off
(LWCO) function of the HydroStat control is active. When the
control is installed with a Hydrolevel Electro-Well, this LED
will be on at all times when the control is powered.
NOTE: If the control was installed with a well other than the
Electro-Well, this LED will not illuminate. This indicates that
the control is providing temperature function only.
LWCO LOW WATER Indicates that the boiler is in a
low water condition. The HydroStat control will prevent
burner operation during this condition. If the LOW WATER
light is blinking, the control has been programmed to provide
lock-out protection in the event a low water condition is
detected (see Manual Reset Low Water Cut-Off on page 5).
Pressing the TEST/SETTINGS button will reset the control.
IMPORTANT: The system must be checked by a qualified
heating professional prior to resuming operation.
WARNING: ALLOW THE BOILER TO FULLY COOL
BEFORE ADDING WATER.
TEST/SETTINGS Button
To Test Low Water Cut-Off: Press and hold the
Test/Settings button for 5 seconds. The display will read
LCO.
LWCO TEST
0000
The red Low Water light should illuminate and the burner
circuit (B1 and B2) should de-energize. NOTE: The control
must be installed with a Hydrolevel Electro-Well for low water
cut-off functionality (see page 1 for more details).
To View Current Settings: Press and release the
Test/Settings Button in short intervals to sequentially display
the following settings:
HIGH LIMIT SETTING
00
HIGH DIFFERENTIAL SETTING
00
LOW LIMIT SETTING
00
LOW DIFFERENTIAL SETTING
00
The display will return to boiler temperature (default) if
Test/Settings Button in not pressed for 5 seconds.
7
LED LEGEND
HydroStat 3150 Instructions Page 7